Load calculation: how much load is on the breaker?
Every socket, fixture and appliance you drop onto the electrical & plumbing layer is connected to a circuit. The simulation adds up the circuit's power and calculates the current, the breaker, the cable size and the voltage drop at the end of the line. The calculation runs in the editor's Simulation step, on the lines you draw; an overloaded line or one over the limit shows up in color on the plan, so you see it before you even call the electrician.
Electrical load calculation: six checks, one board
The simulation runs in the editor's Simulation step: it reads the symbols and the lines you draw and calculates with typical power ratings; if you like, you replace a symbol's power with your own appliance's. Results are listed circuit by circuit; the report can be printed or downloaded as CSV.
01
Circuit load
Every symbol has a power rating: socket 300 W, double socket 600 W, light fixture 60 W, oven 3,000 W, induction hob 7,200 W. A socket next to a washing machine or oven counts as that appliance. The total of the symbols on a circuit is converted into a design current; you can change the value in the right panel to match your own appliance.
02
Breaker selection
The breaker comes from the circuit type: lighting and combi boiler B10; sockets, washing machine, dishwasher, air conditioning and water heater B16; oven B20; induction hob B40 on single-phase, 3 × B16 on three-phase. The type is worked out automatically from the connected appliances. When the breaker load exceeds 80% it turns yellow, above 100% red; you're asked to split a circuit that's over.
03
Cable size
The cable size is first chosen to carry the breaker: 1.5 mm² lighting, 2.5 mm² sockets, 4 mm² oven, 10 mm² single-phase induction hob. If the installation method, ambient temperature and number of circuits on the same route lower the current-carrying capacity, or the voltage drop limit is exceeded, the cable size increases automatically.
04
Voltage drop
The circuit's length is measured on the plan and the voltage drop at the end of the line is calculated. The limit is 1.5% on lighting and socket circuits and 3% on motor circuits (air conditioning) (Turkish Electrical Installations Regulation, Art. 57); on a line over the limit, the cable size automatically goes up one step.
05
Diversity and main breaker
Not all appliances run at the same time. Circuit loads are summed with a demand factor (0.7 for an apartment), and the feeder and main switch are suggested accordingly: C40 · C50 · C63 on three-phase, C40 · C63 on single-phase. Socket and wet-area circuits get a 30 mA RCD, one per four circuits.
06
Warnings
Oven and washing machine on the same circuit, more than eight sockets on one socket circuit, a line without RCD protection in a wet area, a lighting circuit longer than 25 meters, a line passing through a reinforced concrete column or beam: all are marked on the plan; a route around the column recalculates the take-off and the voltage drop. Column–wiring check →
Typical apartment distribution
Which circuit, which cable, which breaker
The values the simulation uses by default. The circuit type is worked out automatically from the connected loads (a socket next to the oven becomes an oven circuit); you can change it in the circuit's properties.
Circuit
Cable
Breaker
Note
Lighting
Room lighting circuit
3 × 1.5 mm²
B10
One or two rooms combined; up to 12 light fixtures
Socket
General socket circuit
3 × 2.5 mm²
B16
Up to 8 sockets per circuit; a separate circuit per room is recommended
Kitchen worktop sockets
3 × 2.5 mm²
B16
Separate circuit; small appliances go here
Washing machine
3 × 2.5 mm²
B16
Each machine on its own circuit
Dishwasher
3 × 2.5 mm²
B16
Each machine on its own circuit
Power
Oven
3 × 4 mm²
B20
Separate circuit, direct connection or power socket
Induction hob
single-phase 3 × 10 mm² · three-phase 5 × 2.5 mm²
B40 · 3 × B16
Separate circuit; on a three-phase supply it's connected to all three phases, with the load split evenly across them
Air conditioner
3 × 2.5 mm²
B16
Separate circuit for each indoor unit; mind the distance to the outdoor unit
Water heater / electric heater
3 × 2.5 mm²
B16
Separate circuit; RCD protection mandatory in wet areas
Combi boiler
3 × 1.5 mm²
B10
Separate circuit, earthed
Distribution board
RCD
—
30 mA
Socket and wet-area circuits; one RCD per four circuits
Supply riser (meter → board)
single-phase 3 × 10 · 3 × 16 mm²
C40 · C63
Based on the total load found with the demand factor; three phase: 5 × 10 mm² C40, 5 × 16 mm² C50, 5 × 25 mm² C63
The values reflect common residential practice; local regulations, the utility company's specifications and the engineer's decision take precedence. Aluminum conductors, surface installation and high ambient temperatures reduce capacity.
Your own conditions
Cable type, installation method and phase for a realistic calculation
It starts with defaults; you change them for the whole project or for a single circuit to match conditions on site.
Supply
Single-phase 230 V or three-phase 400 V; on three-phase, circuits are assigned from largest to smallest to the least loaded phase, and phase imbalance is shown as a percentage
Cable type
NYA (single-core), NYM, NHXMH (halogen-free); order quantity by number of cores
Installation method
In conduit in the wall, in a thermally insulated wall, without conduit, in cable trunking; ambient temperature and the number of circuits on the same route correct the current-carrying capacity
Per circuit
Circuit type, cable, installation, RCD and phase; overrides the default
Conduit
Suggested conduit diameter based on cable size and number of cores (16–32 mm)
Between floors
A circuit on the upper floor is fed from the distribution board via a floor riser; line length and voltage drop account for it
Revision
Save a version of the breaker list; circuits that change afterwards are marked in the list
How it works
Load calculation in three steps: from symbol to breaker
STEP 01
Run circuits from the board
Place the distribution board on the electrical & plumbing layer and run lines to the rooms with the circuit tool. When a circuit point lands on a symbol, the symbol is connected to that line; you can change which breaker feeds it in the circuit's properties. The circuit type (lighting, socket, power) determines the cable and the breaker.
Step 01 · CircuitsGround floor
STEP 02
Change power ratings if needed
Every symbol comes with a typical power rating: socket 300 W, oven 3,000 W, induction hob 7,200 W. If you enter the power (W) from your appliance's label in the symbol's properties, the simulation recalculates instantly.
Step 02 · PowerSymbol
STEP 03
Read the result, download the sheet
The circuit list gives the current, breaker, cable size and voltage drop; any line over the limit shows up in color on the plan. The report can be printed or downloaded as CSV; the breaker, cable size and cable take-off also go into the MEP sheet, and that is what goes to the electrician.
Step 03 · ReportPrint · CSV
Why it's tied to the plan
The load calculation isn't a separate calculator, it's the plan itself
With a separate calculator, you enter the length as a guess. Nodaform measures circuit length from the line you draw on the plan; when you move a socket or change the line, the calculation updates itself.
Line length from the line you draw on the plan, including floor risers
A warning appears if a wet-area or socket circuit has no RCD protection
A line passing through a column or beam lights up red; the length is re-measured along a route around the column
The result is written to the MEP sheet and to the element properties in the BIM model
On revision, differences from the previous breaker list are shown
Input
Electrical symbols, circuit lines, symbol power ratings; cable type, installation method, ambient temperature
Formula
I = P / (U · cos φ) · ΔU = 2 · L · I / (k · A) single-phase, √3 · L · I / (k · A) three-phase · copper k = 56
Circuit list, main switch and feeder, phase distribution, warnings on the plan; report (print) and CSV
Plan
Ultimate · in the editor's Simulation step
Simulation by plan
Voltage and load simulation on Ultimate
FREE
Homeowner · Student · Hobbyist
Plan and furniture layers. The electrical & plumbing tab is locked; you can review the distribution table on this page.
PLUS
Agent · Solo designer
Electrical & plumbing layer: sockets, switches, lighting, distribution board and circuits; wall view in 3D; circuit list and board diagram on the MEP drawing sheet.
PRO
Architect · Interior designer · Contractor
MEP sheet: breaker and cable size from the circuit type, cable and conduit take-off, main switch, RCD and number of distribution board modules; with default conditions. Voltage drop percentages and warnings are on Ultimate.
ULTIMATE
Engineer · Design office · Contractor
Plan-linked load, breaker, cable size and voltage drop; your own cable type, installation method and phase; warnings on the plan, revision difference, report and writing to BIM properties.
FAQ
Frequently asked questions
How are the breaker and cable size suggestions made?
The breaker comes from the circuit type (lighting B10, sockets B16, oven B20, induction hob B40 or 3 × B16 on three-phase). The cable size is chosen to carry the breaker; if the installation method, ambient temperature and number of circuits on the same route lower the current-carrying capacity, or the voltage drop limit is exceeded, the cable size increases automatically.
What is the voltage drop limit?
Following Article 57 of the Turkish Electrical Installations Regulation, Nodaform uses 1.5% for lighting and socket circuits and 3% for motor circuits (air conditioning) as warning thresholds. On a line over the limit, the cable size automatically goes up one step.
Does it work for a three-phase apartment?
Yes. When you select a three-phase supply, circuits are assigned from largest to smallest to the least loaded phase; the induction hob is connected to all three phases. Phase imbalance is shown as a percentage in the simulation panel.
Does this calculation replace an electrical design?
No. The results are a pre-check to discuss with your electrician and electrical engineer; the construction design and approval belong to a licensed engineer.
Which plan includes the simulation?
Plan-linked voltage and load simulation is on the Ultimate plan; it runs in the editor's Simulation step, without opening a separate tool. The MEP sheet on Pro also gives you breakers, cable sizes and cable take-off; voltage drop percentages, warnings and your own conditions are on Ultimate.
Start
Plan and wiring first; the simulation comes on top.
Open a free account and draw the plan; drop in the sockets with Plus, and once you move to Ultimate, breaker, cable size and voltage drop calculations appear automatically on the same plan.
No credit card needed · No install · Paid plans are paid through Paddle