Simulation 01 · ULTIMATE

How much load is on the breaker?

Every socket, fixture and appliance you drop onto the electrical & plumbing layer is connected to a circuit. The simulation adds up the circuit's power and calculates the current, a suitable breaker, the cable size and the voltage drop at the end of the line. The calculation runs inside the editor the moment you finish wiring; an overloaded line lights up red on the plan, so you see it before you even call the electrician.

What does it calculate?
Pre-check · Does not replace an electrical design
B10–B32breaker suggestion
1.5–10mm² cable size
1.5–3%drop limit
30 mAresidual current
Floor Plan · Load Simulation1:100
BED 1BED 2LIVINGBATHKITCHEN DB L5 · 18.3 A · B16 ! CIRCUIT LOAD · 5 LINES L1 Sockets bed 1L2 Sockets bed 2L3 LivingL4 BathL5 Kitchen 6.2 A · B164.8 A · B169.7 A · B162.6 A · B1018.3 A · B16 ! breaker load · over 80% yellow · over 100% red Total installed powerDemand factor 0.65Main switch · feeder 14.9 kW9.7 kW · 42 AC63 · 3×16 mm² RCD 30 mA · sockets and wet areas 12.00 m
What it calculates

Six calculations, one board

The simulation runs inside the editor, right after the electrical & plumbing layer: it reads the symbols, you confirm the power ratings, and the rest is automatic. Results are listed circuit by circuit in the simulation step; the report can be printed or downloaded as CSV.

01

Circuit load

Every symbol has a power rating: socket 300 W, double socket 600 W, light fixture 60 W, oven 3,000 W, induction hob 7,200 W. A socket next to a washing machine or oven counts as that appliance. The total of the symbols on a circuit is converted into a design current; you can change the value in the right panel to match your own appliance.

02

Breaker selection

The smallest standard circuit breaker that carries the design current is suggested: B6, B10, B16, B20, B25, B32. When breaker load exceeds 80% you get a yellow warning, above 100% a red one.

03

Cable size

It checks that the suggested breaker does not exceed the cable's current-carrying capacity. 1.5 mm² for lighting, 2.5 mm² for sockets, 4–6 mm² for oven and hob, 10–16 mm² for the supply riser.

04

Voltage drop

The circuit's length is measured on the plan and the voltage drop at the end of the line is calculated. If it exceeds 1.5% on lighting or 3% on socket and power circuits, a larger cable size or splitting the circuit is suggested.

05

Diversity and main breaker

Not all appliances run at the same time. Circuit loads are summed with a demand factor (0.6–0.7 for an apartment), and the supply riser size and main switch (C40, C63) are suggested accordingly. The RCD is fixed at 30 mA.

06

Warnings

Oven and washing machine on the same circuit, more than eight sockets on one socket circuit, a line without RCD protection in a wet area, a lighting circuit longer than 25 metres, a line passing through a reinforced concrete column or beam: all are marked on the plan; a route around the column recalculates the take-off and the voltage drop. Column–wiring check →

Typical apartment distribution

Which circuit, which cable, which breaker

The values the simulation uses by default. The circuit type is worked out automatically from the connected loads (a socket next to the oven becomes an oven circuit); you can change it in the circuit's properties.

CircuitCableBreakerNote
Lighting
Room lighting circuit3 × 1.5 mm²B10One or two rooms combined; up to 12 light fixtures
Socket
General socket circuit3 × 2.5 mm²B16Up to 8 sockets per circuit; a separate circuit per room is recommended
Kitchen worktop sockets3 × 2.5 mm²B16Separate circuit; small appliances go here
Washing machine3 × 2.5 mm²B16Each machine on its own circuit
Dishwasher3 × 2.5 mm²B16Each machine on its own circuit
Power
Oven / built-in hob3 × 4 mm² · induction 3 × 6 mm²B20 · B32Separate circuit, direct connection or power socket
Air conditioner3 × 2.5 mm²B16Separate circuit for each indoor unit; mind the distance to the outdoor unit
Water heater / electric heater3 × 2.5 mm²B16Separate circuit; RCD protection mandatory in wet areas
Combi boiler3 × 1.5 mm²B10Separate circuit, earthed
Distribution board
RCD—30 mAAll socket and wet-area circuits; a separate RCD is recommended for lighting
Supply riser (meter → board)3 × 10 mm² · 3 × 16 mm²C40 · C63Based on the total load found with the demand factor; 5 cores for three phase

The values reflect common residential practice; local regulations, the utility company's specifications and the engineer's decision take precedence. Aluminium conductors, surface installation and high ambient temperatures reduce capacity.

How it works

Three steps from symbol to breaker

STEP 01

Run circuits from the board

Place the distribution board on the electrical & plumbing layer and run lines to the rooms with the circuit tool. When a circuit point lands on a symbol, the symbol is connected to that line; you can change which breaker feeds it in the circuit's properties. The circuit type (lighting, socket, power) determines the cable and the breaker.

STEP 02

Confirm power ratings

Every symbol comes with a default power rating. Type the value from the oven's label or the air conditioner's BTU rating into the right panel; the simulation recalculates instantly. For appliances you're unsure about, a typical value is suggested.

STEP 03

Read the result, download the sheet

The circuit list gives the current, breaker, cable size and voltage drop; any line over the limit lights up red on the plan. The board schematic and breaker list are added to the MEP sheet as a PDF, and that is what goes to the electrician.

Why it's tied to the plan

Not a calculator, the plan itself

With a separate calculator, you enter the length as a guess. Nodaform measures circuit length from the line you draw on the plan and groups symbols by room; when you move furniture and shift a socket, the calculation updates itself.

  • Line length from the plan, including wall runs and storey height
  • Symbols in wet areas are forced onto an RCD-protected circuit
  • A line passing through a column or beam lights up red; the length is re-measured along an alternative route
  • The result is written to the MEP sheet and to the element properties in the BIM model
  • On revision, differences from the previous breaker list are shown
Input
Electrical symbols, circuit lines, symbol power ratings, cable size
Formula
I = P / (U · cosφ) · ΔU = 2 · ρ · L · I / S (single phase) · ρCu 0.0175 Ω·mm²/m
Standard circuit breakers
B6 · B10 · B16 · B20 · B25 · B32 · C40 · C63
Limits
Lighting ΔU ≤ 1.5% · sockets and power ΔU ≤ 3% · breaker load ≤ 80% recommended
Export
Circuit list, board schematic, breaker list (PDF), warning markers on the plan
Plan
Ultimate · in the editor, right after the electrical & plumbing layer
Simulation by plan

Voltage and load simulation on Ultimate

FREE

Homeowner · Student · Hobbyist

Plan and furniture layers. The electrical & plumbing tab is locked; you can review the distribution table on this page.

PLUS

Agent · Solo designer

Electrical & plumbing layer: sockets, switches, lighting, distribution board and circuit schematic; wall view in 3D. No load calculation.

PRO

Architect · Interior designer · Contractor

MEP sheet, cable take-off and breaker list; default cables and breakers are assigned by circuit type, with no calculation.

ULTIMATE

Engineer · Design office · Contractor

Plan-linked load, breaker, cable size and voltage drop simulation; warnings on the plan, board schematic, written to BIM properties.

FAQ

Frequently asked questions

How are the breaker and cable size suggestions made?

The design current is found from the circuit's total power; the smallest standard breaker that carries that current is chosen and checked against the cable's current-carrying capacity. Voltage drop is calculated from line length and cable size.

What is the voltage drop limit?

Nodaform uses 1.5% for lighting circuits and 3% for socket and power circuits as warning thresholds. For a line over the limit, a larger cable size or a shorter line is suggested.

Does it work for a three-phase apartment?

Yes. When you select a three-phase supply, circuits are balanced across the phases; large loads such as the oven and air conditioner are put on separate phases. Phase balance is shown as a percentage in the simulation panel.

Does this calculation replace an electrical design?

No. The results are a pre-check to discuss with your electrician and electrical engineer; the construction design and approval belong to a licensed engineer.

Which plan includes the simulation?

Plan-linked voltage and load simulation is on the Ultimate plan; it runs in the editor right after the electrical & plumbing layer, without opening a separate tool.

Start

Plan and wiring first; the simulation comes on top.

Open a free account, draw the plan and drop in the sockets. Once Ultimate is unlocked, breaker and cable size calculations come in one click on the same plan.