- Portable extinguishers
- One 6 kg dry chemical powder (or equivalent gas) extinguisher for every 500 m² at low hazard and for every 250 m² at medium and high hazard. At most 25 m from any point to an extinguisher. 4–12 kg extinguishers are hung at a height not exceeding about 90 cm above the floor. Car parks, storerooms and plant rooms also get a wheeled extinguisher. art. 99
- Maintenance
- A general on-site inspection once a year; at the end of the fourth year, the extinguishing agent is renewed and a pressure test is carried out (TS ISO 11602-2) by an authorised company. art. 99/7
- Travel distance
- Without / with sprinklers, one way · two ways: apartment buildings 15 / 30 · 30 / 75 m; offices 15 / 30 · 45 / 75 m; shops, stores 15 / 25 · 45 / 60 m; hotels 15 / 20 · 30 / 45 m. Dead-end corridors 15 m (20 m with sprinklers). Within a flat, at most 20 m from any point to the flat entrance door (30 m with sprinklers); not required in residential buildings with no more than 4 storeys including the basement, or in detached houses. art. 32, 48, Annex 5/B
- Doors, corridors, exits
- Clear door width at least 80 cm, height 200 cm, no threshold. In spaces for more than 50 people, doors open in the direction of escape and are not kept locked; every space for more than 50 people has at least 2 exits. Corridors serving spaces at least 110 cm wide. art. 33, 39, 47
- Fire escape stairs
- In residential buildings up to a building height of 21.50 m, a normal stair is enough; between 21.50 and 30.50 m, at least two stairs, one of them protected; in taller buildings, two protected stairs and a fire safety lobby or pressurisation. Open external escape stairs cannot be used once the building height exceeds 21.50 m. No boiler, meter or air conditioner outdoor unit in the stair enclosure. art. 41, 42, 48
- Sprinkler
- Non-residential buildings over 30.50 m in height, residential buildings over 51.50 m, enclosed car parks larger than 600 m², multi-storey shops and shopping centres over 2000 m² and some accommodation buildings. art. 96
- Detectors at home
- In residential buildings, automatic detection is mandatory only where the building height exceeds 51.50 m. There is no national requirement for smoke and carbon monoxide detectors in homes; fitting them is still recommended. art. 75, Annex 7
- Emergency lighting, signs
- At least 60 minutes on all escape routes (120 minutes in buildings for more than 200 people), at least 1 lux along the centre line of the route. In buildings with more than one exit, a white "ÇIKIŞ" (EXIT) sign on a green background, 200–240 cm above the floor. art. 72, 73
- Evacuation plan
- All workplaces prepare an emergency plan; an evacuation plan showing escape routes and assembly points is posted at eye level at entrances and on each floor. Drills at least once a year. Workplace Emergencies Reg. art. 12, 13
- Commercial kitchens
- Kitchen hood suppression systems, gas detection and gas shut-off in kitchens in shopping centres and high-rise buildings, in catering factories and in kitchens serving more than 100 people at once. art. 57